Specifications for Super T1-40S PLCs

Program

Program Control

Stored Program, Cyclic Scan: Scan is selectable; floating or fixed time.

Language

Ladder diagram with easily inserted function blocks.

Capacity

8192 Steps of Program Memory
4096 Words of Data Registers, 256 Timers, & 256 Counters
Discrete I/O 144 Points max

Program Memory

RAM (capacitor back-up) and EEPROM (no back-up battery required)

RAM memory back-up

1 hour at 25C by built-in capacitor,
2 years at 25C by optional battery

Program capacity

8K steps (4K or 8K mode)

Instructions

Basic: 21, Function: 97 

Execution speed

1.4s/contact, 2.3s/coil, 4.2s/16-bit transfer, 6.5s/16-bit addition

Program types

1 main program
1 sub-program (initial program)
1 timer interrupt (interval: 5 to 1000ms, 5ms units)
4 I/O interrupt (high-speed counter and interrupt input)
256 subroutines (up to 3 levels of nesting)

I/O capacity

Main unit: 16 points (8 inputs/8 outputs)
Expansion I/O: Up to 8 I/O modules (expandable up to 144 points)

User data I/O register

512 points/32 words (X/XW, Y/YW)
Auxiliary relay 4096 points/256 words (R/RW)
Special relay   1024 points/64 words (S/SW)
Timer           256 points (T./T), 64 @ 0.01s & 192 @ 0.1s
Counter         256 points (C./C)
Data register   4096 words (D)
Index register  3 words (I, J, K)

Real-time-clock/calendar

+/-60s/month (not included with ecconomy model

Special I/O functions

High speed counter (2 single or 1 quadrature) or Interrupt input (2 points),
Adjustable analog register (2 points), (Also known as screwdriver inputs)
Pulse output (CW+CCW or pulse+direction) or PWM output

Communications interface

1 port of RS232C (programmer port) Programmer or Computer link protocol
TOSLINE-F10 remote (by using TOSLINE-F10 module)

The following are on the enhanced version only:
1 port of RS485
Computer link mode
(Programmer or Computer) ,
Data link mode,
Free ASCII mode,
Inverter (VF-A7/S9) connection mode

Debug support function

Sampling trace (8 devices and 3 register - 256 times)
On-line programming (at 4K mode)
On-line EEPROM write

Network

Computer link, Tosline F10 (On slelected models)

Environmental

Ambient temperature

0 to 55C (operation), -20 to 75C (storage)

Ambient humidity 

20 to 90% RH, no condensation

Noise immunity

1000V p-p/1??s, 89/336/EEC (EMC directive)

Vibration immunity

9.8m/s2 (1g), (for 30 minutes per axis, on 3 mutually perpendicular axis)

Shock immunity

98m/s2 (10g), (3 shocks per axis, on 3 mutually perpendicular axis)

Supported Standards

UL/c-UL, CE

Dimensions (mm)

T1-16 (L122 x W90 x D74.5), T1-28 (L167.5 x W90 x D82), T1-40 (L167.5 x W90 x D85).

Transistor Output Max current

0.5A  24Vdc

Power

Power supply

AC powered units - 100 to 240Vac (+10%, -15%) 45 VA or less
DC powered units - 24Vdc (+20%, -15%) 18 W or less

5Vdc power for I/O units Max.

1.5A (when 24Vdc service power is not used) (this specification can limit the number of I/O cards)

Service power output Max. 

24Vdc @ 0.2A (power for exciting limit switches and transducers)

Withstand voltage

1500Vac for 1 minute (between power terminals and ground terminal)

Descrete Inputs

Input points 

24 points (24 points/common)

Input voltage - Rated

24Vdc, +10/-15 % (AC version 100 - 120Vac  +10% -15% 50/60Hz)

Input current - Rated

7m A @ 24Vdc (AC version 7mA @ 100Vac)

Minimum ON voltage

15Vdc (AC Version 80Vac)

Maximum OFF voltage

5Vdc (AC Version 30 Vac)

ON/OFF delay time

0 to 15ms (user selectable, default setting is 10ms) (AC version 25 -30ms)

Relay Output Specifications

Output points

14 points (6 Isolated and 2x 4 points/common)

Maximum voltage

240Vac/24Vdc

Maximum Current

2A/point (resistive), 2A/common

Minimum load

5Vdc - 10mA

ON/OFF delay time

10m s or less

DC Output specifications

Output points

2 points (2 points/common)

Maximum voltage

+24Vdc

Maximum Current

0.5A/point (resistive)

Off state Leakage current

0.1m A or less

ON/OFF delay time

0.1m s or less

Terminal block

Non removable with M3 screw