Toshiba PLC T40 TDR140S3S
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Specifications for Super T1-40S PLCs |
|
Program |
|
Program Control |
Stored Program, Cyclic Scan: Scan is selectable; floating or fixed time. |
Language |
Ladder diagram with easily inserted function blocks. |
Capacity |
8192 Steps of Program Memory |
Program Memory |
RAM (capacitor back-up) and EEPROM (no back-up battery required) |
RAM memory back-up |
1 hour at 25C by built-in capacitor, |
Program capacity |
8K steps (4K or 8K mode) |
Instructions |
Basic: 21, Function: 97 |
Execution speed |
1.4s/contact, 2.3s/coil, 4.2s/16-bit transfer, 6.5s/16-bit addition |
Program types |
1 main program |
I/O capacity |
Main unit: 16 points (8 inputs/8 outputs) |
User data I/O register |
512 points/32 words (X/XW, Y/YW) |
Real-time-clock/calendar |
+/-60s/month (not included with ecconomy model |
Special I/O functions |
High speed counter (2 single or 1 quadrature) or Interrupt
input (2 points), |
Communications interface |
1 port of RS232C (programmer port) Programmer or Computer
link protocol |
Debug support function |
Sampling trace (8 devices and 3 register - 256 times) |
Network |
Computer link, Tosline F10 (On slelected models) |
Environmental |
|
Ambient temperature |
0 to 55C (operation), -20 to 75C (storage) |
Ambient humidity |
20 to 90% RH, no condensation |
Noise immunity |
1000V p-p/1??s, 89/336/EEC (EMC directive) |
Vibration immunity |
9.8m/s2 (1g), (for 30 minutes per axis, on 3 mutually perpendicular axis) |
Shock immunity |
98m/s2 (10g), (3 shocks per axis, on 3 mutually perpendicular axis) |
Supported Standards |
UL/c-UL, CE |
Dimensions (mm) |
T1-16 (L122 x W90 x D74.5), T1-28 (L167.5 x W90 x D82), T1-40 (L167.5 x W90 x D85). |
Transistor Output Max current |
0.5A 24Vdc |
Power |
|
Power supply |
AC powered units - 100 to 240Vac (+10%, -15%) 45 VA or less |
5Vdc power for I/O units Max. |
1.5A (when 24Vdc service power is not used) (this specification can limit the number of I/O cards) |
Service power output Max. |
24Vdc @ 0.2A (power for exciting limit switches and transducers) |
Withstand voltage |
1500Vac for 1 minute (between power terminals and ground terminal) |
Descrete Inputs |
|
Input points |
24 points (24 points/common) |
| Input voltage - Rated |
24Vdc, +10/-15 % (AC version 100 - 120Vac +10% -15% 50/60Hz) |
| Input current - Rated |
7m A @ 24Vdc (AC version 7mA @ 100Vac) |
Minimum ON voltage |
15Vdc (AC Version 80Vac) |
Maximum OFF voltage |
5Vdc (AC Version 30 Vac) |
ON/OFF delay time |
0 to 15ms (user selectable, default setting is 10ms) (AC version 25 -30ms) |
Relay Output Specifications |
|
Output points |
14 points (6 Isolated and 2x 4 points/common) |
Maximum voltage |
240Vac/24Vdc |
Maximum Current |
2A/point (resistive), 2A/common |
Minimum load |
5Vdc - 10mA |
ON/OFF delay time |
10m s or less |
DC Output specifications |
|
Output points |
2 points (2 points/common) |
Maximum voltage |
+24Vdc |
Maximum Current |
0.5A/point (resistive) |
Off state Leakage current |
0.1m A or less |
ON/OFF delay time |
0.1m s or less |
Terminal block |
Non removable with M3 screw |